AppDaemon Climate/DHW Control Fails on Negative PVPC Prices

Problem

AppDaemon apps climate_control and dhw_control get stuck in a retry loop:

  • ERROR climate_control: Error getting prices: — note the exception message is empty
  • Telegram notification: Error getting prices: retrying in 10 minutes
  • The aerotherm HVAC is never scheduled (stays in off/DHW-only mode), so the house is not cooled or heated on price-optimized hours

Root Cause

Both apps rejected negative prices: Price.__post_init__ raised a bare ValueError for value < 0. With high solar generation, the Spanish PVPC market now regularly has negative prices during midday hours (e.g. 2026-09-05: -0.0107 €/kWh at 15-16h). As soon as today's price curve contains a negative hour, _get_prices raises and every 10-minute retry fails again — all day long. The bare ValueError renders as an empty string, which is why the log line ends with Error getting prices: and no message. An empty exception message in these logs is the fingerprint of this bug.

How to Diagnose

# Check today's PVPC curve for negative hours
curl -s "https://api.esios.ree.es/archives/70/download_json?locale=es&date=$(date +%F)" \
  | python3 -c "
import json,sys
for r in json.load(sys.stdin)['PVPC']:
    if float(r['PCB'].replace(',', '.')) < 0:
        print(r['Hora'], r['PCB'])
"

# Empty exception message in AppDaemon logs
kubectl --context=grigri -n home-assistant logs -l app=appdaemon --tail=50 | grep "Error getting prices"

Fix / Workaround

Fixed in apps/home-assistant/appdaemon/apps/:

  • Price accepts negative prices (they are legitimate market values, not sensor errors)
  • When today's curve contains negative hours, climate_control sends a separate Telegram message after the schedule notification listing them as merged ranges, e.g. Negative PVPC prices: 12-16h
  • When fetching prices fails entirely (sensor missing/unavailable), both apps register a fallback schedule so the aerotherm keeps working, and keep retrying real data every 10 minutes:
  • climate_control: HVAC runs for min_hours_per_day starting at the current hour
  • dhw_control: DHW is forced at every interval_hours window start (immediately if all window starts for today already passed)

This complements the ESIOS ZIP-response workaround — see pvpc-updated-esios-api-zip-response.md.